9.4
Programming DACT
With the DACT facility, the control unit can use one or two telephone lines, or a single Ethernet connection, to call a supervising station
(remote station or central station) and report a local alarm, trouble, or supervisory condition.
This section describes programming the DACT options to specify the characteristics of the DACT's phone connection, communication
format, and the format of the event or CID codes used by the supervising station.
Login at level 3 before starting DACT programming.
9.4.1
Accessing the DACT program menu
To access the DACT program menu, complete the following steps:
Press MENU.
1.
Press UP or DOWN until the [Programming] option is displayed and then press ENTER. The control unit displays the following:
2.
FIRE ALARM
SUSPENDED
Then a few seconds later, the control unit displays the following:
<ENTER> to PROGRAM
<EXIT> to CANCEL
3.
Press ENTER. The control unit displays the following:
<ENTER>=Accept
Prg: [Points]
4.
Use the UP and DOWN keys to choose [DACT] and press ENTER. The control unit displays the following:
<ENTER>=Accept
DACT: [Options]
Use the UP and DOWN keys to select one of the following choices:
5.
- [Options]
- [Event Codes]
- [CID Points]
DACT Options: With these options, you can program a wide range of DACT parameters like supervising station phone numbers and
account codes.
Note: If no DACT is installed, use this option to disable the DACT.
CID Points: The Contact ID communication format supports per-point reporting of system events.
The supervising station receives a code identifying the point and the event type like Alarm or Trouble. With this format, the DACT can also
send a restoral code to the supervising station after the device experiencing the alarm, trouble, or supervisory condition is restored to a
normal state.
page 30
2008 Foundation Series Fire Alarm Control Unit Operation Guide
579-1401 Rev A