9.2.3

Editing NAC alarm groups

With alarm groups, you can program selective signaling. Assign the NAC an alarm group number from 1 to 99. Assign the same alarm
group number to the initiating devices that you want to control the NAC. Each NAC can be in up to three groups.
To edit an NAC alarm group, complete the following steps:
1.
See
Programming NACs
2.
Press ENTER and then press the UP and DOWN keys until [Alarm Groups] is displayed. Then press ENTER. The control unit
displays the following:
ALARM GROUPS
[99] 00 00
Use the UP and DOWN keys to scroll the number in the brackets. Use the RIGHT and LEFT keys to move between the alarm
3.
groups. Press ENTER when all the values are set correctly.
4.
When NAC programming is complete, press ESC key until the control unit displays the following:
[Cont] Dscrd Save
5.
Select [Save] and press ENTER to save the configuration.