Cautions, Warnings, and Regulatory Information..................3 Introduction..............................4 Inspecting the contents of shipment..............................4 Overview.................................5 City circuit card specifications................................5 Mounting the city circuit card........................7 Communications and power connection....................8 City card configuration..........................9 Configuring the city circuit card................................9 Setting P6.......................................9 Disconnect settings of the city circuit card............................9 Configuring the city circuit card for the 2004-9101 FACU........................9...
Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
This following sections describe the installation procedure for the City Circuit Card with Disconnect Switch 2004-9909. Inspecting the contents of shipment Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify your local Simplex product supplier.
2004 and 2008 Foundation Series Fire Alarm Control Unit City Circuit Card Installation Guide 3 Overview The 2004-9909 city circuit card is used to annunciate alarms and other urgent indications to remote facilities. When the 2004-9101 or 2008-9101 control unit goes into alarm, the city card circuits are activated, and annunciation immediately occurs at the remote facility. Reverse polarity modules or local energy modules, for reaching the Public Service Fire Communications Center, receive annunciations at the remote site.
Page 8
2004 and 2008 Foundation Series Fire Alarm Control Unit City Circuit Card Installation Guide Table 2: City circuit card specifications City circuit card specifications Current Standby current: 30mA Alarm current: 60mA City output voltage ± 24 V nominal, 20 to 32 VDC, fused at 3 A Environmental specifications Operating temperature 32°F to 120°F (0°C to 49°C)
2004 and 2008 Foundation Series Fire Alarm Control Unit City Circuit Card Installation Guide 4 Mounting the city circuit card To mount the city circuit card inside the cabinet, complete the following steps: Remove the AC power at the breaker from the control unit. Use the B-key to unlock the hinged door of the cabinet.
2004 and 2008 Foundation Series Fire Alarm Control Unit City Circuit Card Installation Guide 5 Communications and power connection The city circuit card comes with a power and communication harness. You can use this harness for interfacing the city circuit card with the 2004-9101 or 2008-9101 control unit.
2004 and 2008 Foundation Series Fire Alarm Control Unit City Circuit Card Installation Guide 6 City card configuration Configuring the city circuit card For the city circuit cards, use the information in Table 3 and Setting P6 to set the jumper positions for reverse polarity and local energy operations.
Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks or registered marks.