Description Of Various Functions; Area Readout Mode - Hamamatsu Photonics ORCA-Fire C16240-20UP Instruction Manual

Table of Contents

Advertisement

11. DESCRIPTION OF VARIOUS FUNCTIONS

11-1 AREA READOUT MODE

11-1-1 CAMERA READOUT MODES (READOUT DIRECTION)
The camera reads out in two line pairs simultaneously.
11-1-2 READOUT METHODS
(1) Full resolution readout mode (1×1 readout)
Perform charge readout from camera individually for all pixels.
(2) Binning readout (2×2 / 4×4 readout)
With this camera, 2×2 binning readout and 4×4 binning are available by adding the signal of
adjacent pixels in the digital domain. Binning readout is a method for achieving high sensitivity in
exchange for losing resolution.
(3) Sub-array readout
Sub-array readout is a procedure where only a region of interest is scanned. It is possible to
increase the frame rate by reducing the number of vertical lines scanned. In sub-array readout,
binning can also be enabled.
Size and a position of the readout area can be configured according to the table below.
Minimum settable step of the size and position on the table is in only the case that the camera is used
with DCAM-API.
Refer to 10-1-4 "FRAME RATE CALCULATION" about the frame rate of each readout mode.
Digital CMOS Camera C16240-20UP / C16240-20UP01 Instruction manual_Ver.1.3
Figure 11-1 Readout direction of Area readout mode
Size
Horizontal
Vertical
4 pixels
4 lines
Position
Horizontal
Vertical
4 pixels
4 lines