Versiv Series Cabling Certification Product Family
Users Manual
154
Find Quality Products Online at:
Table 7. Settings for Fiber Tests(cont.)
No. of Con-
Jumper Reference: Enter the number of jumpers you will
use in each fiber path when you set the reference. The
nectors/
dotted lines in the diagram on the screen show you which
Splices
parts of the link are included in the test results. See
(continued)
Reference Method above.
Figure 58 shows the No. of Connectors/Splices screen.
Figure 59 shows how to count the jumpers, connectors, and
splices for this setting.
TRC LENGTH
You can enter length of your test reference cords when you
(Test refer-
set the reference. To enter this value, tap TRC LENGTH on the
ence cord
SET REFERENCE screen. The length you enter does not change
length)
the test results. The tester saves the length with the results to
meet TIA reporting requirements.
D
E
F
G
Figure 58. Screen to Set the Number of Connectors,
Splices, and Jumpers