1 1 T E C H N I C A L S P E C I F I C AT I O N S

11 Technical specifications

11 1 Technical Data Sheet

GENERAL DATA
Output rated power
Output power factor
Topology
Parallel configuration
Inbuilt batteries
INPUT
Nominal input voltage
Input voltage tolerance
Input current THDi
Frequency range
Power factor
OUTPUT
Rated output voltage
Voltage tolerance
Voltage distortion
Overload capacity (linear
load) on inverter
Nominal frequency
Crest factor
EFFICIENCY
Overall system efficiency
In eco-mode
ENVIRONMENT
Protection rating
Storage temperature
Operating temperature
Relative humidity
Altitude (above see level)
BATTERIES
Type
Inbuilt batteries
Charging current
Recharge time (inbuilt batteries) 4h to 90%
COMMUNICATIONS
User interface
Optional communication cards
STANDARDS
Safety
EMC
Performance
Manufacturing
WEIGHT, DIMENSIONS
Weight
Dimensions w x h x d
G2 1kVA B/ S
G2 2kVA B/ S
900 W
1'800W
0.9
0.9
Online double conversion
No
No
Yes/No
Yes/No
220/230/240 VAC
100-300 VAC (load dependent)
5% with full resistive load
45-55 Hz / 54-66 Hz
≥0.99
220/230/240 VAC
±1% (referred to 230V)
<2% linear load, <6% non linear load
60s: 106-130% load
10s: 131-150% load
300ms: ≥ 150% load
50 or 60 Hz
3:1 (load supported)
Up to 89%
Up to 91%
Up to 97.5%
Up to 98%
IP20
UPS: -25°C to 60°C; Batteries: 0°C to 35°C
0°C to 40°C
0% to 95%
1000m without derating
VRLA (valve regulated lead-acid)
2x9.4 Ah (B)
4x9.4Ah(B)
1.5A/3-6A
1.5A/1.5-6A
adjustable
adjustable
LCD display
SNMP;ModBus;AS400;Environmental monitoring sensor probe
IEC/EN 62040-1
IEC/EN 62040-2
IEC/EN 62040-3
ISO 9001:2015, ISO 14001:2015, OHSAS 18001
9.2/3.9 Kg
17.4/6.4 Kg
144x228x356 mm
190x327x399 mm
102x228x346mm
102x327x390 mm
25
G2 3kVA B/ S
2'400W
0.9
No
Yes/No
Up to 91%
Up to 98%
6x9.4Ah(B)
1.5A/1.5-6A
adjustable
22.7/6.4 Kg
190x327x399 mm
102x327x390 mm