Co-Linear With Solid Fuel Fireplace - Valor 1000JN Installation Manual

Direct vent zero clearance gas fireplace
Table of Contents

Advertisement

Venting
Conversion to Co-Linear Liners with a Solid
Fuel Fireplace
Note: Co-linear liners must only be installed within
a solid fuel burning fi replace and chimney when
converting at unit.
The appliance can be adapted to co-linear applications
using an existing fi replace and cavity. The appliance
must not be connected to a chimney fl ue serving a
separate solid-fuel burning appliance.
This requires an approved Co-Axial to Co-Linear
appliance adapter, two lengths of 2-ply, 3" diameter
fl exible chimney liners approved for venting gas
appliances, a co-linear termination kit and fl ashing
or a co-linear to co-axial adapter and either a high
wind vertical vent terminal cap or a low profi le vertical
termination.
If the fi replace has an opening in the installation area,
the appliance can be partially or completely inserted into
the cavity as illustrated to the right.
If partially inserted, the appliance should be installed
within a fully framed wall, consistent with a New
Construction application as described in this document.
Firebox zero clearance standoff s supplied with the heater
are not required when installing completely within a non-
combustible cavity.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictors are not required when using co-linear vent-
ing.
Note: Co-linear fl exible aluminum venting
should be professionally inspected periodically
for corrosion and damage and replaced when
necessary. If the installation does not allow for
future inspection or replacement of the fl exible
aluminum venting, then stainless steel vent liners
should be used.

Co-linear with Solid Fuel Fireplace

Co-Linear installation fully inserted into existing fi replace -
Conversion at unit
Approved
3x3 co-linear
termination
Any fi nishes
applied around
the fi replace's
opening must
be non-
combustible.
Listed
clearances to
combustible
materials apply
Co-Linear installation partially inserted into existing fi replace -
Conversion at unit
Any fi nishes
applied around the
fi replace's opening
must be non-
combustible.
Listed clearances
to combustible
materials apply
Framed
Wall
Engin n e
Engine
Flashing
2 x 3" liners
3" minimum
bending
radius
46DVA-CLAA,
46DVA-GCL
Engine
Engine
or equivalent
co-linear
adapter
46DVA-CLAA,
46DVA-GCL
or equivalent
co-linear
adapter
Approved
3x3 co-linear
termination
Flashing
2 x 3" liners
3" minimum
bending
radius
29