Venting

Co-Linear Conversion Installations

Note: Co-linear portion of vent system may only be
installed within a solid-fuel burning fi replace and
chimney.
The appliance can be adapted to co-linear applications
using an existing chimney. The appliance must not be
connected to a chimney fl ue serving a separate solid-
fuel burning appliance.
The appliance must be fully enclosed while maintaining
clearances to combustibles detailed elsewhere in this
manual.
Types of Installations
• Partial installation into an existing fi replace
• Installation into an adjacent chimney
See the following pages for each installation details.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Set to Position 4 (see page 21).
Note: Co-linear fl exible aluminum venting should be
professionally inspected periodically for corrosion
and damage and replaced when necessary. If the
installation does not allow for future inspection or
replacement of the fl exible aluminum venting, then
stainless steel vent liners should be used.
24