Installation Recommendation For Viscosity Function - Siemens SITRANS FC620 Operating Instructions Manual

Coriolis flowmeters
Table of Contents

Advertisement

Sensor installation

12.4.3 Installation recommendation for viscosity function

In order to use this function an external differential pressure transmitter (separate order)
measuring the pressure difference at the flow line is necessary. The accuracy of the
estimated viscosity is strongly depending on the accuracy of the pressure transmitter and
the correct position and implementation of the pressure taps.
The needed pressure taps have to be placed at the flow line at approximately 4D – 5D
NOTICE
upstream and downstream of the SITRANS FC sensor. The differential pressure
transmitter is directly connected via analog input to the SITRANS FC transmitter (analog
input function must be available).
HART
Fig. 73: Positioning of pressure taps / HART communication line
y
x
6
2
Mounting flanges
Pressure taps
SITRANS FC with HART
5
3
1
1
4
Differential pressure transmitter
with HART
HART communication
Other flow elements
A5E52748375-AA, 2023/09
FC6x0
Installation
x
y
2
6
107 / 194
D

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fc640

Table of Contents