Transmitter; Hart And Modbus Communication; Hart Communication; Modbus Communication - Siemens SITRANS FC620 Operating Instructions Manual

Coriolis flowmeters
Table of Contents

Advertisement

FC6x0
Wiring

13.4 Transmitter

13.4.1 HART and Modbus communication

13.4.1.1 HART communication

HART interface
For devices with HART communication, the HART interface, along with the analog signal,
is available at the output Iout1. A load resistance of 230 – 600 Ω at Iout1 is
recommended.
How to connect to the communication tools is described in the applicable Function
Manual (FM) A5E52748515.

13.4.1.2 Modbus communication

Modbus interface
Modbus interface of SITRANS FC is implemented in accordance with "MODBUS over
serial line specification and implementation guide V1.02", for details of instrumentation
see website of the Modbus organization (http://www.modbus.org/).
Modbus connections Tab. 49: Connection terminal assignment for Modbus
Terminal
I/O3 -
I/O4 +
I/O4 -
ROTAMASS
SITRANS FC
Fig. 83: MODBUS communication
Modbus cable
3-Wire cable (twisted pair (D0, D1) and Common) with shield should be used. Wire gauge
should be AWG24 or wider.
SITRANS FC has a RS485 electrical interface, operating in slave mode and
communicating with the following default specification:
Default Modbus
▪ Modbus baud rate: 19200 bps
setting
▪ Modbus transfer mode: RTU
▪ Modbus parity: Even
▪ Modbus stop bit: 1 stop bit
For further details, see applicable Function Manual (FM) A5E52748619.
126 / 194
MODBUS_B
IO4+
MODBUS_A
IO4-
MODBUS_C
IO3-
A5E52748375-AA, 2023/09
Description
Modbus C (Common)
Modbus B (D1)
Modbus A (D0)
RD+
RS485
RD-
Modem
GND
Transmitter