Common Specifications - Mitsubishi Electric FR-A520-2.2K Instruction Manual

Transistorized inverter, high function & low acoustic noise
Hide thumbs Also See for FR-A520-2.2K:
Table of Contents

Advertisement

6.1.2 Common specifications

Control system
Output frequency range
Frequency
Analog input
setting
resolution
Digital input
Frequency accuracy
Voltage/frequency
characteristic
Starting torque
Torque boost
Acceleration/deceleration
time setting
DC dynamic brake
Stall prevention operation
level
Analog input
Frequency
setting
Digital input
signal
Start signal
Multi-speed selection
Second, third
acceleration/
deceleration time
selection
Jog operation
selection
Current input selection
Output stop
Alarm reset
Operation functions
Operating status
Alarm (inverter trip)
For meter
Operating
status
PU (FR-DU04
/FR-PU04)
Alarm
definition
Operating
Additional
status
display on
Alarm
parameter unit
definition
(FR-PU04)
Interactive
only
guidance
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Soft-PWM control/high carrier frequency PWM control (V/F control or
advanced magnetic flux vector control can be selected)
0.2 to 400Hz
0.015Hz/60Hz (terminal 2 input: 12 bits/0 to 10V, 11 bits/0 to 5V, terminal 1 input: 12 bits/−10
to +10V, 11 bits/−5 to +5V)
0.01Hz
Within ±0.2% of maximum output frequency (25°C ±10°C (77°F ±18°F) for analog input, within
0.01% of set output frequency for digital input
Base frequency set as required between 0 and 400Hz. Constant torque or variable torque
pattern can be selected.
150%: At 0.5Hz (for advanced magnetic flux vector control)
Manual torque boost
0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern
acceleration/deceleration mode can be selected.
Operation frequency (0 to 120Hz), operation time (0 to 10 s), voltage (0 to 30%) variable
Operation current level can be set (0 to 200% variable), presence or absence can be selected.
0 to 5VDC, 0 to 10VDC, 0 to ±10VDC, 4 to 20mADC
3-digit BCD or 12-bit binary using operation panel or parameter unit
(when the FR-A5AX option is used)
Forward and reverse rotation, start signal automatic self-holding input (3-wire input) can be
selected.
Up to 15 speeds can be selected. (Each speed can be set between 0 and 400Hz, running
speed can be changed during operation from the PU (FR-DU04/FR-PU04).)
0 to 3600 seconds (up to three different accelerations and decelerations
can be set individually.)
Provided with jog operation mode select terminal (Note 1)
Input of frequency setting signal 4 to 20mADC (terminal 4) is selected.
Instantaneous shut-off of inverter output (frequency, voltage)
Alarm retained at the activation of protective function is reset.
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input
selection, polarity reversible operation, automatic restart operation after instantaneous power
failure, commercial power supply-inverter switch-over operation, forward/reverse rotation
prevention, slip compensation, operation mode selection, offline auto tuning function, online
auto tuning function, PID control, programmed operation, computer link operation (RS-485)
5 different signals can be selected from inverter running, up to frequency, instantaneous power
failure (undervoltage), frequency detection, second frequency detection, third frequency
detection, during program mode operation, during PU operation, overload alarm, regenerative
brake pre-alarm, electronic overcurrent protection pre-alarm, zero current detection, output
current detection, PID lower limit, PID upper limit, PID forward/reverse rotation, commercial
power supply-inverter switch-over MC1, 2, 3, operation ready, brake release request, fan fault
and fin overheat pre-alarm minor fault. Open collector output.
Contact output...change-over contact (230VAC 0.3A, 30VDC 0.3A)
Open collector...alarm code (4 bit) output
1 signal can be selected from output frequency, motor current (steady or peak value), output
voltage, frequency setting, running speed, motor torque, converter output voltage (steady or
peak value), regenerative brake duty, electronic overcurrent protection load factor, input power,
output power, load meter, and motor exciting current. Pulse train output (1440 pulses/sec./full
scale) and analog output (0 to 10VDC).
Selection can be made from output frequency, motor current (steady or peak value), output
voltage, frequency setting, running speed, motor torque, overload, converter output voltage
(steady or peak value), electronic overcurrent protection load factor, input power, output power,
load meter, motor exciting current, cumulative energization time, actual operation time,
watt-hour meter, regenerative brake duty and motor load factor.
Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.
(Four alarm definitions are only displayed on the operation panel.)
Input terminal signal states, output terminal signal states, option fitting status, terminal
assignment status
Output voltage/current/frequency/cumulative energization time
immediately before protective function is activated
Operation guide and troubleshooting by help function
192