Applied motor (Pr. 71)

Pr. 71 "applied motor"
Set the motor used.
Parameter
Factory
Number
Setting
71
0
0 to 8, 13 to 18, 20, 23, 24
<Setting>
·
Refer to the following list and set this parameter according to the motor used.
Pr. 71
Thermal Characteristics of Electronic Overcurrent Protection
Setting
0
Thermal characteristics matching a standard motor
1
Thermal characteristics matching the Mitsubishi constant-torque motor
Thermal characteristics matching a standard motor
2
5-point flexible V/F characteristics
Thermal characteristics for advanced magnetic flux vector control of the Mitsubishi
20
standard motor SF-JR4P (1.5KW (2HP) or less)
3
Standard motor
13
Constant-torque motor
Mitsubishi general-purpose motor SF-JR4P
23
(1.5KW (2HP) or less)
4
Standard motor
14
Auto tuning data can be read or set anew.
Mitsubishi general-purpose motor SF-JR4P
24
(1.5KW (2HP) or less)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
7
Standard motor
17
Constant-torque motor
8
Standard motor
18
Constant-torque motor
·
For the 5.5K and 7.5K, the Pr. 0 and Pr. 12 settings are automatically changed depending on the Pr. 71
setting.
Pr. 71
0, 2, 3 to 8, 20, 23, 24
Pr. 0
3%
Pr. 12
4%
Note: 1. When "9999" is set in Pr. 19, "2" cannot be set in Pr. 71. To set "2" in Pr. 71, set the appropriate
value (other than "9999") in Pr. 19.
2. When "2" is set in Pr. 71, Pr. 100 to Pr. 109 are displayed on the parameter unit (FR-PU04). In
other settings, if any of Pr. 100 to Pr. 109 settings is changed, the new setting is not displayed in
the "Default parameter list" and "Set parameter list".
3. Refer to Pr. 96 for offline auto tuning.
4. Set any of "3, 7, 8, 13, 17 and 18" to perform offline auto tuning.
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting Range
Select "offline auto tuning setting".
Constant-torque motor
Star connection
Delta connection
Star connection
Delta connection
1, 13 to 18
2%
2%
CAUTION
93
PARAMETERS
Related parameters
Pr. 0 "torque boost"
Pr. 12 "DC dynamic brake voltage"
Pr. 19 "base frequency voltage"
Pr. 60 "intelligent mode"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 96 "auto tuning setting/status"
Pr. 100 to Pr. 109 "
V/F frequency/voltage"
Motor
Standard
{
{
{
{
{
{
{
{
Motor constants can
{
be entered directly.
{
Direct motor
{
constant entry and
offline auto tuning
Constant
Torque
{
{
{
{
{
{
{

Advertisement

Table of Contents
loading

Table of Contents