Selection and protection of a motor
4.9.2

Applied motor (Pr. 71, Pr. 450)

Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function
suitable for the motor is set.
When General-purpose magnetic flux vector or Advanced magnetic flux vector control is selected, the motor constants
(SF-JR, SF-HR, SF-JRCA, SF-HRCA, etc.) necessary for control are selected as well.
Parameter
Number
71
Applied motor
450
Second applied motor
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 183)
(1) Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Pr. 71 (Pr. 450)
Setting
Thermal Characteristic of the Electronic Thermal Relay Function
Pr. 71
Pr. 450
0
Thermal characteristics of a standard motor
(Pr. 71 initial value)
1
Thermal characteristics of the Mitsubishi constant-torque motor
40
Thermal characteristic of Mitsubishi high efficiency motor (SF-HR)
50
Thermal characteristic of Mitsubishi constant-torque motor (SF-HRCA)
3
Standard motor
13
Constant-torque motor
Mitsubishi standard motor
23
(SF-JR 4P 1.5kW or less)
43
Mitsubishi high efficiency motor (SF-HR)
Mitsubishi constant-torque motor (SF-
53
HRCA)
4
Standard motor
14
Constant-torque motor
Mitsubishi standard motor
24
(SF-JR 4P 1.5kW or less)
44
Mitsubishi high efficiency motor (SF-HR)
Mitsubishi constant-torque motor (SF-
54
HRCA)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
9999
(initial
Without second applied motor
value)
∗1
Motor constants of Mitsubishi high efficiency motor SF-HR.
∗2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
REMARKS
When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in Pr. 71.
(Refer to page 116 for offline auto tuning.)
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
Automatic Change
Parameter
Pr. 0
Pr. 12
∗1
Pr. 71 setting: 0, 3 to 6, 23, 24,40, 43, 44
∗2
Pr. 71 setting: 1, 13 to 16, 50, 53, 54
114
Initial
Name
Value
0
9999
Standard Motor
Setting ∗1
3%
4%
Setting Range
0, 1, 3 to 6, 13 to 16,
Selecting the standard motor or constant-torque
23, 24, 40, 43, 44,
motor sets the corresponding motor thermal
50, 53, 54
characteristic.
0, 1
Set when using the second motor.
Second motor is invalid
9999
(thermal characteristic of the first motor
(Pr. 71))
Select "Offline auto tuning setting"
Auto tuning data can be read,
changed, and set.
Star
Direct input of
connection
motor constants is
Delta
enabled
connection
Constant-torque Motor
Setting ∗2
2%
2%
Description
Motor ( : Used motor)
Standard
Constant-torque
(SF-JR, etc.)
(SF-JRCA, etc.)
∗1
∗2
∗1
∗2
∗1