Operation Selection Function Parameters

3.6 Operation Selection Function Parameters

3.6.1

Applied motor (Pr. 71)

Set the motor used.
POINT
When using the Mitsubishi constant-torque motor, set "1" in Pr. 71.
The electronic overcurrent protection is set to the thermal characteristic of the
constant-torque motor.
When you selected the Mitsubishi constant-torque motor, the values of the following
parameters are automatically changed. (For factory settings only)
Pr. 0 "torque boost", Pr. 12 "DC injection brake voltage"
Parame
Name
ter
71
Applied motor
<Setting>
Refer to the following list and set this parameter according to the motor used.
Pr. 71 Setting
Thermal Characteristics of Electronic Overcurrent Protection
0
Thermal characteristics matching a standard motor
1
Thermal characteristics matching the Mitsubishi constant-torque motor
Set this parameter correctly according to the motor used. Incorrect setting may
cause the motor to overheat and burn.
3.6.2

PWM carrier frequency (Pr. 72)

You can change the motor sound.
Parame
Name
ter
72
PWM frequency selection
<Setting>
Parameter Number
72
REMARKS
•An increased PWM frequency will decrease motor noise but noise and leakage current will
increase. Take proper action. (Refer to page
•Metallic sound may be generated from the motor at sudden deceleration but it is not a fault.
Factory
Setting
0
CAUTION
Factory
Setting
1
Setting
PWM carrier frequency can be changed.
0 to 15
The setting displayed is in [kHz].
Note that 0 indicates 0.7kHz and 15 indicates 14.5kHz.
Setting
Range
0, 1
Setting
Range
0 to 15
Description
)
28.
70