Applied Motor (Pr. 71, Pr. 450) - Mitsubishi Electric FR-E720-600 Instruction Manual

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

4.9.2

Applied motor (Pr. 71, Pr. 450)

Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function
suitable for the motor is set.
When general-purpose magnetic flux vector or advanced magnetic flux vector control is selected, the motor constants
(SF-JR, SF-HR, SF-JRCA, SF-HRCA, etc.) necessary for control are selected as well.
Parameter
Name
Number
71
Applied motor
450
Second applied motor
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 180)
(1)
Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Pr. 71 (Pr. 450)
Setting
Thermal Characteristic of the Electronic Thermal Relay Function
Pr. 71
Pr. 450
0
Thermal characteristics of a standard motor
(Pr. 71 initial value)
1
Thermal characteristics of the Mitsubishi constant-torque motor
40
Thermal characteristic of Mitsubishi high efficiency motor SF-HR
50
Thermal characteristic of Mitsubishi constant torque motor SF-HRCA
3
Standard motor
13
Constant-torque motor
Mitsubishi standard motor
23
(SF-JR 4P 1.5kW or less)
43
Mitsubishi high efficiency motor (SF-HR)
Mitsubishi constant-torque motor (SF-
53
HRCA)
4
Standard motor
14
Constant-torque motor
Mitsubishi standard motor
24
(SF-JR 4P 1.5kW or less)
44
Mitsubishi high efficiency motor (SF-HR)
Mitsubishi constant-torque motor (SF-
54
HRCA)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
9999
(initial
Without second applied motor
value)
∗1
Motor constants of Mitsubishi high efficiency motor SF-HR.
∗2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
REMARKS
When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in Pr. 71.
(Refer to page 113 for offline auto tuning.)
For the FR-E720-240 and 330, FR-E740-120 and 170, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage
settings are automatically changed according to the Pr. 71 setting as follows.
Automatic Change
Parameter
Pr. 0
Pr. 12
∗1
Pr. 71 setting: 0, 3 to 6, 23, 24,40, 43, 44
∗2
Pr. 71 setting: 1, 13 to 16, 50, 53, 54
Initial
Setting Range
Value
0, 1, 3 to 6, 13 to 16,
0
23, 24, 40, 43, 44,
50, 53, 54
9999
Select "Offline auto tuning setting"
Auto tuning data can be read,
Star
connection
Delta
connection
Standard Motor
Constant-torque Motor
Setting ∗1
Setting ∗2
3%
4%
Selection and protection of a motor
Selecting the standard motor or constant-torque
motor sets the corresponding motor thermal
characteristic.
0, 1
Set when using the second motor.
Second motor is invalid
9999
(thermal characteristic of the first motor
(Pr. 71))
Standard
(SF-JR, etc.)
changed, and set.
Direct input of
motor constants is
enabled
2%
2%
Description
Motor ( : Used motor)
Constant torque
(SF-JRCA, etc.)
∗1
∗2
∗1
∗2
∗1
∗2
111
4