4.8.2

Applied motor (Pr. 71, Pr. 450)

Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function
suitable for the motor is set.
When General-purpose magnetic flux vector is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
etc.) necessary for control are selected as well.
Parameter
Number
71
Applied motor
450
Second applied motor
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 163)
(1)
Set the motor to be used
Refer to the following list and set the parameter according to the motor used.
Pr. 71 (Pr. 450)
Setting
Thermal Characteristic of the Electronic Thermal Relay Function
Pr. 71
Pr. 450
0
Thermal characteristics of a standard motor
(Pr. 71 initial value)
1
Thermal characteristics of the Mitsubishi constant-torque motor
40
Thermal characteristic of Mitsubishi high efficiency motor (SF-HR)
50
Thermal characteristic of Mitsubishi constant-torque motor (SF-HRCA)
3
Standard motor
13
Constant-torque motor
Mitsubishi standard motor
23
(SF-JR 4P 1.5kW or lower)
43
Mitsubishi high efficiency motor (SF-HR)
53
Mitsubishi constant-torque motor (SF-HRCA)
9999
(initial
Without second applied motor
value)
∗1
Motor constants of Mitsubishi high efficiency motor SF-HR.
∗2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
REMARKS
When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in Pr. 71.
(Refer to page 106 for offline auto tuning.)
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
Automatic Change
Parameter
Pr. 0
Pr. 12
∗1
Pr. 71 setting: 0, 3, 23, 40, 43
∗2
Pr. 71 setting: 1, 13, 50, 53
NOTE
Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when using a
geared motor (GM-S, GM-D, GM-SY, GM-HY2 series) to perform General-purpose magnetic flux vector control.
104
Initial
Name
Value
0
9999
Standard Motor
Setting ∗1
3%
4%
Setting Range
Selecting the standard motor or constant-torque
0, 1, 3, 13,
motor sets the corresponding motor thermal
23, 40, 43, 50, 53
characteristic.
0, 1
Set when using the second motor.
Second motor is invalid.
9999
(thermal characteristic of the first motor
(Pr. 71))
Select "Offline auto tuning
setting"
Constant-torque Motor
Setting ∗2
2%
2%
Description
Motor ( : Used motor)
Standard
Constant-torque
(SF-JR, etc.)
(SF-JRCA, etc.)
∗1
∗2
∗1
∗2