Huawei UPS5000-A-400K-SL User Manual page 62

40 kva power modules
Table of Contents

Advertisement

UPS5000-A-(400 kVA-500 kVA)
User Manual (40 kVA Power Modules)
Item
Recommended cross-
sectional area (mm
When there is one mains input, configure input cables as mains input cables.
Additionally, cables listed in
If external conditions such as cable layout or ambient temperatures change, perform verification in
accordance with the IEC-60364-5-52 or local regulations.
You must abide by the local rules and regulations when bridging and wiring AC cables.
The currents listed in
multiply the currents by 0.95; if the rated voltage is 415 V, multiply the currents by 0.92.
If primary loads are non-linear loads, increase the cross-sectional areas of neutral wires 1.5–1.7 times.
When you connect power cables, comply with the tightening torque listed in
ensure secure connections and prevent safety risks.
Table 3-6 Power cable connector requirements
Connector
Mains input
connector
Bypass
input
connector
Battery
input
connector
Output
connector
Issue 06 (2020-01-10)
+
2
)
N
-
PE
Table 3-5
Routing mode: Routed over the ladder or bracket in a single layer (the routing mode for DC cables is
F in IEC60364-5-52 and the routing mode for AC cables is E in IEC60364-5-52).
Ambient temperature: 30° C
The drop amplitude of AC voltage is less than 3% and DC voltage less than 1%. The length of the
AC power cables of a 400 kVA or 500 kVA UPS is no longer than 30 m and DC power cables no
longer than 50 m.
90° C copper flexible cable
Table 3-5
Connection Mode
Crimped OT terminals
Crimped OT terminals
Crimped OT terminals
Crimped OT terminals
Copyright © Huawei Technologies Co., Ltd.
are available only under the following conditions:
are measured at a rated voltage of 380 V; if the rated voltage is 400 V,
Bolt
Type
M16
M16
M16
M16
400 kVA
500 kVA
3 x 185
4 x 150
3 x 185
4 x 150
3 x 185
4 x 150
185
240
Table 3-6
Bolt Hole
Diameter
18 mm
18 mm
18 mm
18 mm
3 Installation
to
Torque
120N•m
120N•m
120N•m
120N•m
54