Diagnostic alarms input and output module DIQ 8x24VDC
A diagnostics alarm is output for each diagnostics event. On the I/O device DIQ 8x24VDC, the
LED ER/MS flashes red. You can read out the diagnostics alarms in the diagnostics buffer of
the CPU, for example. You can evaluate the error codes with the user program.
Table 5- 8
Diagnostics
alarm
Wire break
Parameter error
Load voltage 2L+
missing
Hardware inter-
rupt lost
Short-circuit
See also
Diagnostics function manual
(https://support.industry.siemens.com/cs/ww/en/view/59192926)
CM 8x IO-Link + DIQ 8x24VDC M12-L 8xM12 (6ES7148-6JJ00-0BB0) communications module
Equipment Manual, 12/2022, A5E51718265-AB
Diagnostics alarms, their meanings and corrective measures
Error
Meaning
code
6
Fault in the external circuitry.
H
Encoder faulty.
Impedance of sensor circuitry is
too high
Interruption of cable between the
I/O device and sensor.
Channel not connected (open).
10
I/O device cannot evaluate
H
parameters for the channel
Incorrect configuration
11
Load voltage 2L missing or too
H
low.
16
The I/O device cannot trigger an
H
interrupt because the previous
interrupt was not acknowledged;
possible configuration error.
105
Short-circuit to L+
H
106
Short-circuit to ground.
H
PROFINET IO
5.2 Interrupts/diagnostics alarms
Corrective measures
Check the external circuitry and
correct the fault.
Replace the encoder.
Use a different encoder type or
modify the wiring. For example,
use cables with a larger cross-
section.
Establish the connection.
Disable diagnostics
Connect a resistor of 25 kΩ to
45 kΩ to the encoder contacts.
Correct the parameter assign-
ment.
Check the supply voltage on the
I/O device.
Change the interrupt handling
on the CPU and reassign the
parameters to the I/O device, if
necessary.
The error persists until the I/O
device is assigned new param-
eters.
Correct the process wiring.
Replace the defective encod-
er/actuator.
45