5.2.3

Alarms

The IO-Link master can generate diagnostic alarms of the type (severity) "Diagnostics" or
"Maintenance" on behalf of the IO-Link device or the IO-Link port.
• Alarms of the "Diagnostics" type indicate a malfunction of the IO-Link device / port and
should be corrected immediately.
• Alarms of the "Maintenance" type indicate a maintenance demand. The aim is to detect
and eliminate potential faults at an early stage, even before functionality is impaired.
• Hardware interrupt events signal the corresponding process states on the IO-Link device
(e.g. limit exceeded)
5.2.3.1

Diagnostics alarms

IO-Link master error types
All IO-Link events of the type Error generated by the IO-Link device or port are mapped to the
PROFINET diagnostics alarm of the type (severity) "Diagnosis" of the assigned submodule.
IO-Link device diagnostics
The IO-Link master generates PROFINET channel diagnostics (CET, ECET) from the IO-Link
events of an IO-Link device according to the following mapping regulations:
In the "IO-Link Device Diagnostics - Page 1" (CET 0x9500
range 0x0000 - 0x7FFF
ECET
In the "IO-Link Device Diagnostics - Page 2" (CET 0x9501
range 0x8000 - 0xFFFF
ECET
Table 5- 6
IO-Link event
code
0x0000 -
0x7FFF
0x8000 -
0xFFFF
Example of displaying the IO-Link event codes:
An IO-Link device generates event code 0x4000
The channel diagnostics from the event code:
• PROFINET channel diagnostics type: Diagnosis, CET: 0x9500
Diagnostics alarm "IO-Link Device Diagnostics - Page 1, Temperature fault - Overload",
generated from the IO-Link event code 0x4000
IO-Link port diagnostics
The IO-Link master generates channel diagnostics for each port. The port-specific channel
diagnostics are shown in the port diagnostics (CET 0x9502
CM 8x IO-Link + DIQ 8x24VDC M12-L 8xM12 (6ES7148-6JJ00-0BB0) communications module
Equipment Manual, 12/2022, A5E51718265-AB
are displayed directly:
H
= IO-Link Event Code
H
H
are displayed directly:
H
= (IO-Link Event Code
H
H
Overview of error types IO-Link device diagnostics
Error type
(CET)
0x9500
H
(38144
)
H
D
0x9501
H
(38134
)
H
D
– 0x8000
)
H
Extended error
Error text
type (ECET)
0x0000 - 0x7FFF
Error /
H
(0 - 32767
)
warning
D
0x0000 - 0x7FFF
Error /
H
(0 - 32767
)
warning
D
(type "Error")
H
.
H
5.2 Interrupts/diagnostics alarms
) the IO-Link event codes in the
H
) the IO-Link event codes in the
H
Meaning
See the manual of the IO-Link de-
vice or IODD file used.
See the manual of the IO-Link de-
vice or IODD file used.
.