13.4 Mechanical and climatic ambient conditions
13.3

Shipping and storage conditions

Introduction
The CPU 1515SP PC2 exceeds the requirements of IEC 61131‑2 in terms of shipping and storage
conditions. The following information applies to modules that are shipped and/or stored in their
original packaging.
Table 13-6
Shipping and storage conditions for modules
Type of condition
Free fall (in shipping package)
Temperature
Barometric pressure
Relative humidity
Sinusoidal vibrations according to
IEC 60068‑2-6
Shock according to IEC 60068-2‑27
13.4

Mechanical and climatic ambient conditions

Operating conditions
The CPU 1515SP PC2 is suitable for use in weather-proof, fixed locations. The operating
conditions are based on the requirements of DIN IEC 60721‑3‑3:
• Class 3M3 (mechanical requirements)
• Class 3K3 (climatic requirements)
Mechanical ambient conditions
The table below shows the mechanical ambient conditions in the form of sinusoidal oscillations.
Table 13-7
Frequency band
5 Hz ≤ f ≤ 8.4 Hz
8.4 Hz ≤ f ≤ 150 Hz
Table 13-8
Frequency band
5 Hz ≤ f ≤ 8.2 Hz
8.2 Hz ≤ f ≤ 500 Hz
86
Mechanical environmental conditions for BA 2×RJ45
 
3.5 mm amplitude
1 g constant acceleration
Mechanical environmental conditions for BA 2×FC
CPU 1515SP PC2
7.5 mm amplitude
2 g constant acceleration
Permissible range
≤1 m
From -40 °C to +70 °C
from 1140 hPa to 660 hPa (corresponds to an altitude of ‑1000
m to 3500 m)
5% to 95%, without condensation
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
Operating Instructions, 03/2023, A5E42603425-AC