Industrial OS

The functions described in the following chapter apply only to the Open Controller CPU 1515SP
PC2 (F) V30.0 SIMATIC Industrial OS.
12.1

Updating BIOS

A physical access to the CPU 1515SP PC2 is not required. An SSH connection is sufficient.
Procedure
Proceed as follows to update the BIOS:
1. Download the BIOS update file from Siemens Industry Online Support
support.industry.siemens.com/cs/ww/en/view/109743969).
2. Transfer the BIOS update file to the CPU 1515SP PC2.
3. Run the following command as root: bios-update <FILE>
4. The CPU 1515SP PC2 is automatically restarted twice.
A log file is created in the home directory of root. The file contains complete information
about the BIOS update process. If an error is detected, a service data dump is added to this log
file.
5. After the required number of restarts, check the log file.
If it says "All done" at the end, then the BIOS update was successful.
Otherwise check the error message and contact Siemens Industry Online Support if
necessary. Provide the log file to the Siemens Industry Online Support.
Note
It is recommended to run the BIOS update in native Linux mode.
12.2

Commissioning procedure

When you start the Open Controller CPU 1515SP PC2 for the first time, the installations of
SIMATIC Industrial OS and Software Controller are started automatically.
The detailed description of the configuration of Simatic Industrial OS can be found in
Industrial OS - Getting Started, section 2.4.
view/109795683)
Before installing the Software Controller, the customer must accept the license terms,
security information, and OSS and third party licenses. The system performs several restarts
during the installation process.
More information about installation and operation of the software controller can be found
in the Operating Instructions Software Controller CPU 1505SP (F), CPU 1507S (F) and
CPU 1515SP PC2 (F/T/TF)