  • Page 2 ___________________ Preface ___________________ Guide to documentation ___________________ SIMATIC Product overview ___________________ Wiring ET 200SP DQ 4x24..230VAC/2A ST digital ___________________ Parameter output module assignment/addressing (6ES7132-6FD00-0BB1) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 03/2015 A5E32043575-AB...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Conventions CPU: When the term "CPU" is used in this manual, it applies to the CPUs of the S7-1500 automation system as well as to the CPUs/interface modules of the ET 200SP distributed I/O system. STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the configuration and programming software "STEP 7 (TIA Portal)".
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Guide to documentation .......................... 6 Product overview ............................ 8 Properties ..........................8 Wiring ..............................10 Wiring and block diagram ....................... 10 Parameter assignment/addressing ......................12 Parameters ..........................12 Explanation of parameters ...................... 13 Address space ........................14 Interrupts/diagnostics alarms .........................
  • Page 6: Guide To Documentation

    Guide to documentation The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 7 Guide to documentation Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). My Documentation Manager The My Documentation Manager is used to combine entire manuals or only parts of these to your own manual.
  • Page 8: Product Overview

    Product overview Properties Article number 6ES7132-6FD00-0BB1 View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③ ⑨ 2D matrix code Function and firmware version ④ ⑩ Wiring diagram Color code for selecting the color identification labels ⑤...
  • Page 9 The following accessories must be ordered separately: ● Labeling strips ● Color identification labels ● Reference identification label You can find more information on accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...
  • Page 10: Wiring

    Wiring and block diagram This section includes the block diagram of the DQ 4x24..230VAC/2A ST module with the terminal assignments for 2-wire and 3-wire connection. You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system system manual. NOTICE Dangerous voltage.
  • Page 11 Wiring 3.1 Wiring and block diagram Connection: 2-wire and 3-wire connection of actuators The following figure shows the block diagram and an example for the terminal assignment of the digital input module DQ 4x24..230VAC/2A ST on the BaseUnit BU type B1. ①...
  • Page 12: Parameter Assignment/Addressing

    Only for configuration using the PROFIBUS GSD file; does not affect configuration with STEP 7 using HSP: As the number of parameters with PROFIBUS GSD configuration is limited to a maximum of 244 bytes per ET 200SP station, the configuration options are limited. If required, however, you can still set this parameter using data record 128 as de- scribed in the column "GSD file PROFINET IO"...
  • Page 13: Explanation Of Parameters

    Determines whether a channel is enabled or disabled. Reaction to CPU STOP Determines the behavior of the module in the event of a CPU STOP. See also ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...
  • Page 14: Address Space

    Parameter assignment/addressing 4.3 Address space Address space Configuration options of DQ 4×24..230VAC/2A ST The following configurations are possible: ● Configuration 1: Without value status ● Configuration 2: With value status Evaluating the value status An additional byte is allocated in the input address space if you enable the value status for the digital module.
  • Page 15: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and fault displays LED display The figure below shows the LED displays of the DQ 4×24..230VAC/2A ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED displays Meaning of the LEDs The following tables explain the meaning of the status and error displays. DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...
  • Page 16 DIAG LED Table 5- 1 Error display of the DIAG LED DIAG LED Meaning Backplane bus supply of the ET 200SP not OK Off
 Module parameters not assigned Flashes Module parameters assigned and no module diagnostics Module parameters assigned and module diagnostics...
  • Page 17: Load Voltage Status

    Interrupts/diagnostics alarms 5.2 Load voltage status Load voltage status Load voltage status The firmware of the module cannot detect the status of the load voltage. If the "Load voltage status" function tied to the server module is used, a "1" is always displayed in the status bit for a slot with the DQ 4×24..230VAC/2A ST.
  • Page 18: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DQ 4×24...230VAC/2A ST 6ES7132-6FD00-0BB1 Product type designation DQ 4x24 ... 230VAC/2A General information Firmware version V1.0 FW update possible • Usable BaseUnits BU type B1 Color code for module-specific color identification CC41 label Product function I&M data...
  • Page 19 Technical specifications 6.1 Technical specifications 6ES7132-6FD00-0BB1 Digital outputs Number of outputs Sinking output Sourcing output Short-circuit protection No; install a fuse with 10A trigger current when using a type B1 BU Switching capacity of outputs With resistive load, max. With lamp load, max. 100 W Output voltage For signal "1", min.
  • Page 20 Insulation Insulation tested with DC 2545 V 2 s (routine test) Dimensions Width 20 mm Weights Weight, approx. 50 g Dimension drawing See the manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/59753521) DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...
  • Page 21: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record The data records of the module have an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. Parameter assignment in the user program You can change the parameters of the module in RUN.
  • Page 22 Index Header information The figure below shows the structure of the header information. Figure A-2 Header information DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...
  • Page 23 Index Parameters The figure below shows the structure of the parameters for channels 0 to 3. You enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure byte x to x+1 for the channels 0 to 3 DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual, 03/2015, A5E32043575-AB...