Application planning
5.5 Hardware configuration
5.5

Hardware configuration

As soon as one of the following rules applies, the maximum configuration has been reached.
Maximum mechanical configuration
Backplane bus length: Maximum 1 m mounting width (without CPU 1515SP PC2, including
server module)
Electrical maximum configuration
The number of operable I/O modules of a potential group is limited by the
• Power consumption of the I/O modules
• Power consumption of the components supplied via these I/O modules
The maximum current-carrying capability of the terminals on the BaseUnit L+/ground is 10 A.
USB load
When using the CPU 1515SP PC2 with the maximum configuration, the USB load must also
be considered:
• Horizontal mounting:
– Ambient temperature of 55 °C or higher with max. 32 ET 200SP modules:
• Vertical mounting:
– Ambient temperature of 45 °C or higher with max. 32 ET 200SP modules:
Address space
The address space is predefined. However, you can adjust the address space in the user program.
38
4 x 0.3 A USB load; CFAST memory card max. 10% load; SD card not used 
4x 0.3 A USB load; CFAST memory card and SD card max. 10% load
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 03/2023, A5E42603425-AC