1.3

Shipping and storage conditions for modules and backup batteries

Shipping and storage of modules
S7-400 modules surpass the requirements of IEC 61131-2 with respect to shipping and storage
requirements. The following details apply to modules shipped and/or stored in their original
packing.
Climatic conditions correspond to IEC 60721-3-3, Class 3K7 for storage and IEC 60721-3-2,
Class 2K4 for transportation.
Mechanical conditions are compliant with IEC 60721-3-2, Class 2M2.
Table 1-5
Free fall
Temperature
Barometric pressure
Relative humidity (at +25° C)
Sinusoidal vibration in accord‐
ance with IEC 60068-2-6
Shock in accordance with IEC
60068-2-29
Shipment of backup batteries
Backup batteries should always be shipped in their original package. No special measures are
required for the transport of the backup batteries used in the S7-400 system. The lithium
component of the backup battery is less than 0.5 g.
Storing backup batteries
Always store backup batteries in a cool and dry place. The batteries have a maximum shelf
life of 10 years.
Risk of injury, material damage, release of hazardous substances.
Lithium batteries can explode if handled improperly. Their improper disposal may result in
the release of hazardous substances. Strictly adhere to the following instructions:
Do not throw a new or low battery into an open fire and do not perform any soldering work
on the cell casing (max. temperature 100° C). Do not recharge the battery - risk of explosion!
Do not open a battery. Replace a faulty battery only with the same type. Replacement
batteries can be ordered from SIEMENS (for order numbers, refer to the
Specifications" reference manual , in Appendix C (Page 429)).
Always try to return low batteries to the manufacturer or deliver these to a registered recycling
company.
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
1.3 Shipping and storage conditions for modules and backup batteries
Shipping and storage conditions for modules
WARNING
Permissible range
≤ 1m (to 10 kg)
-40 to +70° C
1080 to 660 hPa (corresponds to an elevation of -1000 to 3500 m)
5 to 95%, without condensation
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
General specifications