Technical specifications

16.4 Shipping and storage conditions

16.4
Shipping and storage conditions
Introduction
The S7-1500 automation system / ET 200MP I/O system meet the specifications regarding
transport and storage conditions pursuant to IEC 61131-2. The following information applies
to modules that are shipped and/or stored in their original packaging.
Shipping and storage conditions for modules
Table 16- 6
Type of condition
Free fall (in shipping package)
Temperature
Barometric pressure
Relative humidity
Sinusoidal vibrations in accordance with IEC
60068-2-6
Shock in accordance with IEC 60068-2-27
322
Shipping and storage conditions
Permissible range
≤ 1 m
from -40 °C to +70 °C
from 1140 to 660 hPa (corresponds to an eleva-
tion of -1000 to 3500 m)
5% to 95%, without condensation
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
System Manual, 12/2017, A5E03461182-AE