Cable Specifications; Ac Input Cable For The Power Cabinet; Dc Power Installation Cables - ABB Terra HP Generation 3 CE Instruction Manual

175 kw static dc system
Table of Contents

Advertisement

12.19

Cable specifications

12.19.1

AC input cable for the power cabinet

Parameter
Cores
Cross section range
Conductor
Diameter of the phase conductors
Insulation
Minimum nominal voltage Uo/U
Minimum test voltage
Ambient temperature range
Diameter of the PE conductor
12.19.2

DC power installation cables

The below data are specific for the DC power cables between the power cabinet and
the charge post.
Parameter
Type
Number of cores
Cross section range (minimum)
Cross section range (maximum)
Diameter
Maximum length
Conductor
Diameter of the phase conductors
Insulation
Nominal voltage Uo (Phase to ground
nominal voltage) /U (Phase to phase
nominal voltage)
Minimum test voltage
Ambient temperature range
Maximum cable temperature (on the sur-
face)
9AKK107992A2254-EN | 005
Specification
3 wires + PE, according to IEC 60446
185 mm² to 240 mm² (365 kcmil to 474
kcmil)
Bare copper, fine wired, bunch stranded,
according to VDE 0295 Cl.5/IEC Cl.5
Refer to the local rules.
PVC that is serviceable for outdoor use,
UV-protected, and oil resistant
450/750 VAC
4 kV
-40 °C to +80 °C (-40 °F to +176 °F)
The same as the diameter of the phase
conductors
Specification
1x Positive, 1x negative cable
Flexible
Unshielded
1
185 mm² (365 kcmil)
300 mm² (592 kcmil)
27 to 35 mm (1.1 to 1.4 in)
60 m (197 ft)
Fine wire, stranded in tin plated copper
or aluminum, according to VDE 0295
cl.5/IEC Cl.5
Refer to the local rules.
Rubber or PVC that is serviceable for
outdoor use, UV-protected, and oil re-
sistant
600/1000 Vac - 900/1500 Vdc
6 kV
-40°C to 80°C (-40 °F to 176 °F)
+90°C (+194 °F)
Technical data
91