Electrical Installation Requirements (Europe) - ABB Terra HP Generation 3 CE Instruction Manual

175 kw static dc system
Table of Contents

Advertisement

Technical data
Parameter
EMC rating for the charge post
EMC rating for the power cabinet
12.6

Electrical installation requirements (Europe)

Parameter
Circuit breaker
Surge protection device
70
Specification
The charge post complies with these
standards:
EN 61000-6-3 : 2007 + A1: 2001 Emis-
sion standard for residential, com-
mercial and light-industrial environ-
ments (Class B)
EN 61000-6-2 : 2005 Immunity for in-
dustrial environments
EN 301489-1 V2.2.0 : 2017
The charge post also complies with the
less strict requirements in these stand-
ards:
EN 61000-6-4: 2007 + A1: 2011 Emis-
sion standard for industrial environ-
ments (Class A)
EN 61000-6-1 : 2007 Immunity for
residential, commercial and light-in-
dustrial environments
The power cabinet complies with these
standards:
EN 61000-6-4:2007 + A1 Emission
standard for industrial environments
(Class A)
EN 61000-6-2: 2005 Immunity for in-
dustrial environments
If the power cabinet must comply
with Class B (residential), install an ex-
ternal EMC filter: Schaffner type FN
3359HV-400-99. To order this part, give
the global ID: 6AGC079955. When this
external EMC filter is installed, the power
cabinet complies with this standard:
EN 61000-6-3 : 2007 + A1 2011 Emis-
sion standard for residential, com-
mercial and light-industrial environ-
ments (Class B)
Specification
Use a circuit breaker with the option for
an under voltage release device.
For example, refer to TMAX XT5 320 A
tuned according to type C or similar.
Type 2
9AKK107992A2254-EN | 005