Danfoss VLT 3006 Product Manual page 91

Table of Contents

Advertisement

Parameter description
103
Motor power
(Motor power)
104
Motor voltage (U
)
M,N
(Motor voltage)
105
Motor frequency (f
)
N
(Motor freq)
90
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
(Depending on unit)
Undersize
[0]
Rated size
[1]
Oversize
Value:
Only for 200-230 V units
200 V
220 V
230 V
Only for 380-415 V units
380 V
400 V
415 V
Only for 440-500 V units
440 V
460 V
500 V
Value:
50 Hz (50 Hz)
60 Hz (60 Hz)
87 Hz (87 Hz)
100 Hz (100 Hz)
Depending on unit
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
Function:
Selection of connected motor size in kW.
This data value is e.g. used for automatic
setting of other motor parameters 107-113.
[2]
Description of choices:
Read rated motor output in kW from the
motor's type plate and select this value. If
this value deviates significantly from the
setting options, select the closest low or
high value (under- or oversize). The para-
meters 107-113 must then be optimized
manually with standard settings for motors
from 0.55-200 kW.
Select the rated motor output (V) on the
motor plate.
[0]
Parameters 107-113 are changed auto-
[1]
matically.
[2]
All values can be addressed via the bus.
It is possible to select 440 V motor voltage
on a 400 V unit. This can be used to
[3]
[4]
optimise motor voltage on using e.g. a
[5]
440 V motor on 415 V mains voltage.
If the VLT
types 3060-3250 is factory set
®
to 500 V, so that the lowest motor voltage
[6]
[7]
which can be selected is 440 V, this can be
[8]
adjusted in parameter 650 by changing the
data values to the same VLT
V mains voltage.
Select the rated motor frequency (Hz) on the
motor plate. If a motor for 220/230 V
[0]
is connected to a 380/415 V frequency
[1]
converter, the default value (50 Hz) must be
[2]
changed to 87 Hz. Parameters 107-113 are
[3]
changed automatically.
1.. Load and motor
type, but 400
®