Cooling
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Mechanical installation
To enable the VLT
®
to get rid of the
cooling air, there must be a free air space
both above and below the VLT
minimum spacing requirements depend
®
on the VLT
type and enclosure.
Model 3002-3052
The following applies to VLT
®
Note that the VLT
s can be installed
without side spacing, but it must be
possible to move the hinges freely.
The following applies to VLT
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
See the dimensioning tables.
The following applies to VLT
®
. The
3052:
Enclosure grade
IP 00
IP 21
IP 20
IP 54
®
types 3060-3150 with wall installation:
Model
3060-3075
3100-3150
®
types 3100-3250 with floor installation:
Model
3100-3150
3200-3250
Note! The side spacing to the next VLT
must be 130 mm due to the base's air
intake on the side.
VLT
®
types 3060-3250 are equipped with
a fan in the front door to cool the internal
components. A distance permitting free
opening of the door is sufficient in front of
the VLT
®
VLT
3060-3250".
®
types 3002-
A
100 mm
100 mm
200 mm
150 mm
A
B
170
25
230
25
A
B
230
130
260
130
®
. See the section: "Door radius
®
43