Warnings
(Continued)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Display messages
Motor overloaded (MOTOR TIME):
According to the electronic thermal motor
protection, the motor is too hot. The war-
ning only appears if "warning" has been se-
lected in parameter 315. See curve p. 130.
Inverter overloaded (INVERT TIME):
The electronic thermal inverter protection
reports that the VLT
®
frequency converter is
close to cutting out due to overload (current
too high for too long). The counter for
electronic thermal inverter protection has
reached 98% (100% gives trip).
Voltage limits:
®
VLT
3000 Series
Undervoltage
Voltage warning low
Voltage warning high
(Brake option used,
parameter 300)
Overvoltage
The voltages stated are the VLT
voltage is the intermediate circuit voltage divided by
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
24 V fault (NO 24 VOLT):
24 V voltage supply from power section to
control card is absent.
EEPROM fault (EEPROM ERROR):
EEPROM fault, data changes are not
saved when the mains voltage is switched
off.
3x200/230 V
3x380/415 V
[VDC]
[VDC]
210
400
235
440
370
665
(395)
(705)
410
730
®
's intermediate circuit voltage, the equivalent mains
2.
3x440/500 V
VLT
3060-3250
®
[VDC]
[VDC]
460
470
510
480
800
790
(845)
(820)
880
850
125