Parameter description
600
Operation data
(Operation data)
601
Data log
(Data log)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
* 0 Total operation hours (tot.hrs xxxx) *)
1 Running hours (run hrs xxxx) *)
2 kWh (energy xxxx)
3 Number of cut-ins (pow.ups xxxx)
4 Number of overheatings (ov.temp xxxx)
5 Number of overvoltages (ov. volt xxxx)
0
1
2
Digital input
[0]
Control word
[1]
Status word
[2]
Reference %
[3]
Frequency out [4]
Phase current [5]
D.C. voltage
[6]
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
Function:
[Index 000.00-005.00]
Display of most important operation data.
Description of choices:
Display range: Total number of operation
hours/running hours/kWh is 0.0-99999
(under 10000 with 1 decimal).
Number of cut-ins/number of overheatings/
number of overvoltages is 0-99999.
Serial communication: Total number of
operation hours/running hours/kWh returned
as floating comma values.
Number of cut-ins/number of overheatings/
number of overvoltages returned as whole
figures.
Total number of operation hours/running
hours/kWh reset automatically after manual
initialization.
NB: The stated data is saved every 8 hours.
kWh can be reset via parameter 011.
Operation hours can be reset via parameter
012.
Number of cut-ins/number of overheatings/
number of overvoltages saved as they
occur.
Function:
3
4
-
- 19
(Index 000.00-019.06)
Logging of data for the last few seconds of
operation.
Description of choises:
Digital inputs stated in hex code (0-FF).
Control word stated in hex code (0-FFFF)
for bus operation RS 485, see p. 75.
Status word stated in hex code (0-FFFF)
for bus operation RS 485, see p. 77.
Reference states the control signal as a
percentage (0-100%).
Frequency out states the unit's output
frequency in Hz (0.0-999.9).
Phase current is the unit´s output current in
A (0.0-999.0).
D.C. voltage states the intermediate circuit
voltage in [VDC] (0-999).
6..Service and diagnostics
119