Parameter description
407
Signal output 42
(Output 42)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
Control ready (control ready)
Unit ready (unit ready)
Unit ready remote control
(UNT RDY RCTL)
Enabled (enabled no WR)
Running (running)
Running no warning
(running no WR)
Running in range
(RUNinRANGE)
Speed = reference no warning
(RUN@REF no WR)
Alarm (alarm)
Alarm or warning (alarm or warn)
Current limit (current limit)
Out of frequency range
(OUT FRQ RGE)
Out of current range
(OUT CURR RGE)
0 - 100 Hz
0-20 mA
0 - 100 Hz
4-20 mA
0 - f
0-20 mA
MAX
0 - f
4-20 mA
MAX
REF
- REF
0-20 mA
MIN
MAX
REF
- REF
4-20 mA
MIN
MAX
FB
- FB
0-20 mA
MIN
MAX
FB
- FB
4-20 mA
MIN
MAX
0 - I
0-20 mA
MAX
0 - I
4-20 mA
MAX
0 - I
0-20 mA
LIM
0 - I
4-20 mA
LIM
0 - T
0-20 mA
MOTOR, RATED 100%
0 - T
4-20 mA
MOTOR, RATED 100%
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
At signal outputs 42 and 45, selection can
[0]
be made between 3 types of signal: 24 V
[1]
(max. 40 mA), 0-20 mA or 4-20 mA.
Signal 24 V is used to indicate selected
[2]
status and warnings; 0-20 mA and
[3]
4-20 mA are used for analogue reading.
[4]
[0]
VLT
ready for use.
®
[5]
[1]
VLT
ready for use.
®
[2]
VLT
set at remote control and ready
®
[6]
for use.
[3]
VLT
ready, no warning.
®
[7]
®
[4]
VLT
running (output frequency
[8]
> 0.5 Hz or start signal).
[9]
[5]
®
VLT
running (output frequency
[10]
> 0.5 Hz or start signal), no warning.
[6]
VLT
running in programmed
®
[11]
frequency range and/or current
parameters, no warning.
[12]
[7]
VLT
output running on reference, no
[13]
®
[14]
warning.
[15]
[8]
Output activated by alarm.
[16]
[9]
Output activated by alarm or warning.
[17]
[10] Current range in parameter 209
[18]
exceeded.
[19]
[11] Motor running out of the program-
[20]
med frequency range in parameters
[21]
210-211.
[22]
[12] Motor running out of the program-
[23]
med current range in parameters
[24]
212-213.
[25]
[13] 0-100 Hz used to read the actual
[26]
[14] output frequency, disregarding the
frequency in parameter 202 (f
[15] 0-f
used to read out the actual
MAX
[16] output frequency, where f
indicated in parameter 202.
[17] REF
-REF
MIN
MAX
[18] range equivalent to the sum of
analogue and pulse input ranges in
parameters 401, 412 and 413, and
bus reference (parameter 516).
[19] FB
-FB
sets the output signal
MIN
MAX
[20] range equivalent to the feedback
signal range selected in parameters
401, 412 or 413.
[21] 0-I
sets the output signal range
MAX
[22] from 0 to I
N x 1.6.
[23] 0-I
sets the output signal range
LIM
[24] from 0 to current limit I
parameter 209.
[25] 0-T
indicates the output sig-
MOTOR, RATED
nal
[26] range from 0 to the highest permitted
torque calculated by the frequency
converter.
4.. Inputs and outputs
).
MAX
is
MAX
sets the output signal
recorded in
LIM
109