Parameter description
517
Store data values
(Store data)
118
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
Off (OFF)
On (ON)
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
5..Serial communication
Function:
[0]
Data values changed via serial bus com-
[1]
munication are not saved automatically
when the mains voltage is switched off,
and therefore parameter 517 must be used
to save changed data values.
Description of choices:
When "to" is selected, it takes approx. 10
sec. to save all parameters' data values,
and parameter 517 then automatically
takes the value "from". Only the data
values in the active menu setup are saved,
i.e. the save function must be performed in
each of the setups used.
Note:
The save function can only be activated
®
when the VLT
frequency converter has
stopped.