Parameter description
403
Binary input 19
(Input 19)
104
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
Reversing (reversing)
Start − rev (start rev.)
No operation (no operation)
Reversing
Start with reversing
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
4.. Inputs and outputs
Description of choices:
Reversing is selected if it is to be possible to
[0]
change the motor's speed direction.
[1]
Logical "0" to terminal 19 will not give
[2]
reversing.
Logical "1" to terminal 19 will give reversing.
The motor can only start if simultaneously
with a signal to terminal 19 a start command
is given to e.g. terminal 18.
Start with reversing is selected if start and
reversing are to be activated with one
input.
If pulse start is selected in para. 402,
the same function is changed automatically
to pulse start with reversing.
NB:
If the start command (logic "1") is given to
terminals 18 and 19 simultaneously, the
motor is stopped.
No operation:
As para. 402.