Danfoss VLT 3006 Product Manual page 111

Table of Contents

Advertisement

Parameter description
408
Signal output 45
(Output 45)
409
Relay output 01
(Relay 01)
110
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
Control ready (control ready)
Unit ready (unit ready)
Unit ready remote control
(UNT RDY RCTL)
Enabled (enabled no WR)
Running (running)
Running no warning
(running no WR)
Running in range
(RUNinRANGE)
Speed = reference no warning
(RUN@REF no WR)
Alarm (alarm)
Alarm or warning (alarm/warn)
Current limit (current limit)
Out of frequency range
(OUT FRQ RGE)
Out of current range
(OUT CURR RGE)
0 - 100 Hz
0-20 mA
0 - 100 Hz
4-20 mA
0 - f
0-20 mA
MAX
0 - f
4-20 mA
MAX
REF
- REF
0-20 mA
MIN
MAX
REF
- REF
4-20 mA
MIN
MAX
FB
- FB
0-20 mA
MIN
MAX
FB
- FB
4-20 mA
MIN
MAX
0 - I
0-20 mA
MAX
0 - I
4-20 mA
MAX
0 - I
0-20 mA
LIM
0 - I
4-20 mA
LIM
0 - T
0-20 mA
MOTOR, RATED 100%
0 - T
4-20 mA
MOTOR, RATED 100%
Value:
Control ready (control ready)
Unit ready (unit ready)
Unit ready remote control
(UNT RDY RCTL)
Enabled (enabled no WR)
Running (running)
Running no warning (RUNNING NOWR) [5]
Running in range
(RUNinRANGE)
Speed = reference no warning
(RUN@REF no WR)
Alarm (alarm)
Alarm or warning (alarm/warn)
Current limit (current limit)
Out of frequency range
(OUT FRQ RGE)
Out of current range
(OUT CURR RGE)
Motor thermal overload
(mot. therm.W)
Ready and no motor
thermal overload
(ready-mot.OK)
Ready and no motor (rdy.mot.rem) [15]
Ready and no over/undervoltage
(ready + D.C. V ok)
Motor magnetized (motor mag.)
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
See breakdown of parameter 407.
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
You can use relay outputs 01 and 04 to
[0]
indicate status and warnings.
[1]
The relay is activated when the conditions
[2]
for the selected data values are fulfilled.
[3]
[4]
Activation/deactivation can be delayed in
parameters 316 and 317.
[6]
When relay output 01 is not active there
is connection between terminals 01 and
[7]
terminal 03, but no connection between
[8]
terminal 01/03 and terminal 02.
[9]
(Changeover contact).
[10]
Description of choices:
[11]
[0] [12]: See explanation in parameter 407
[17]. Motor magnetized must be selected
[12]
for use of the relay for brake control with
external brake. (See description of brake
[13]
control on p. 69).
[14]
[16]
[17]
4.. Inputs and outputs