Danfoss VLT 3006 Product Manual page 116

Table of Contents

Advertisement

Parameter description
502
Data read-out
(Data readout)
(Continued)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
5.. Serial communication
Index 18:
A decimal value to be converted to a 16-bit
binary code. Each bit represents an alarm
according to the table below. When an
alarm is given, the equivalent bit has the
value "1".
Bit
Alarm
0
Trip locked
1
Control card or option card fault
2
Current limit
3
Not used
4
Not used
5
Auto optimization
6
Motor overloaded
7
Inverter overloaded
8
Inverter fault
9
Undervoltage
10
Overvoltage
11
Overcurrent
12
Ground fault
13
DC supply fault
14
Over temperature
15
Thermistor input activated, see
parameter 400/terminal 16
A further description of alarms is given on
pp. 124-125.
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents