Parameter description
014
Power Up Mode
(Power-up mode)
86
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Value:
Auto restart in local operation, use
saved ref. (Auto restart)
Stopped in local operation, use
saved ref. (Loc=Stop)
Stopped at local operation, set ref.
to 0 (Loc=Stp+Ref=0)
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
0.. Operation and display
Function:
Initial situation for Local Start/Stop, Local
Reference (para. 004) and Freeze Refer-
[0]
ence (para. 400, 401 or 405) can be selec-
ted on start up (mains connection).
[1]
Description of choices:
Auto Restart in Local Operation, use saved
[2]
ref. is selected if the unit is to start up with
the references/values which applied on
power off.
Stopped on Local Operation, use saved
ref. is selected if the unit is to remain stop-
ped on mains connection until the start
command is given. After start command
®
the VLT
runs with the saved references.
Stopped on local operation, set ref. to 0
is selected if the unit is to remain stopped
on mains connection. Local Reference
(para. 004) and Freeze Reference (para.
400, 401 or 405) are set at zero.
If remote control is used together with a
Freeze Reference function on power off,
Freeze Reference will be set at zero on
mains connection. The speed must there-
fore be reset with the Speed-Up function
(e.g. para. 406).
NB!
On remote controlled operation, the restart
function will always be "Auto Restart". If the
unit is to remain stopped after mains
connection, Pulse start in para. 402 must
be selected. However, it is a condition that
the start function is not activated.