Technical specifications
11.3 Rated conditions
Digital output (DO), terminals 31 and 32
Maximum supply voltage U
"Conductive" state
"Locked" state
"Locked" is also the status if the device is faulty or analog input
(AI) is = 0 mA.
11.3
Rated conditions
Rated conditions
Ambient conditions for operation according to IEC 60068-2
•
Ambient temperature
•
Maximum permissible height above sea level
•
Relative humidity
Pollution degree according to IEC 61010-1
Overvoltage category according to IEC 61010-1
Enclosure degree of protection
•
In accordance with IEC 60529
•
In accordance with NEMA 250
Corrosion protection according to EN ISO 9227 and
EN ISO 12944
•
6DR710 polycarbonate enclosure
•
6DR711 aluminum enclosure
Vibration resistance
•
Harmonic oscillations (sine) according to
IEC 60068-2-6
•
Bump (half-sine) according to
IEC 60068-2-27
•
Noise (controlled digitally) according to
IEC 60068-2-64
Climate class
•
Storage
•
Transport
62
H
35 V
•
Permissible rated current 50 mA
•
Maximum terminal voltage 3 V
•
Overload-proof
I < 60 µA
For use indoors and outdoors.
-20 ... +80 °C (-4 ... +176 °F)
Up to 2000 m
0 ... 100%
2
II
IP66
Type 4X
C5‑M medium durability
C5‑M medium durability
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axis
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axis
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axis
According to IEC/EN 60721-3
1K23, -40 ... +80 °C (-40 ... +176 °F)
2K13, -40 ... +80 °C (-40 ... +176 °F)
Operating Instructions, 06/2023, A5E50188938-AF
SIPART PS100