Electrical Connection; Pneumatic Connection - Siemens SIPART PS100 Operating Instructions Manual

Electropneumatic positioners
Table of Contents

Advertisement

5.3

Electrical connection

Figure 5-1
5.4

Pneumatic connection

Supply pressure PZ
For safety reasons, the supply pressure PZ can be fed after installation only if the positioner is
switched to the "NO INIT" mode when an electrical signal is available.
Note
Specifications regarding air quality
Observe the specifications regarding the air quality, see section "Technical specifications
> Pneumatic data (Page 63)".
Note
Leakage
Besides continuous air consumption, a leakage can cause the positioner to try to compensate
the position deviation. This will result in premature wear in the entire control device.
• Check if there is leakage with "LEAKAGE TEST".
• If there is leakage, check the pneumatic connections for leaks.
Structure of pneumatic connection (Page 34)
SIPART PS100
Operating Instructions, 06/2023, A5E50188938-AF
Digital input or switching amplifier
Power source 12 to 30 V DC
HART connector
Signal source 4 to 20 mA
Wiring diagram
WARNING
5.4 Pneumatic connection
Digital output
Analog output of position feedback
Analog input current input 4 to 20 mA
Digital input (floating contact)
Connecting
33