Commissioning
6.2 Local commissioning
3. Key in 999.
Press CLEAR
C.ALL.
4. Reset complete. (Reset takes several seconds to complete.)
6.2.10

Using units or percent (%)

Many parameters can be viewed either as a percentage, or in measurement units (P005).
View the parameter, then press MODE
6.2.11

Quick start wizards

6.2.11.1

Quick setup for local operation (outline)

Set the Quick Start parameters between P001 and P010 (the main settings that apply to all
applications and make the system operational). Then set P837 and P838 to ignore false
echoes, and return to RUN mode.
1. Select a language option, or numeric, for the auxiliary reading (P010).
2. Select the measurement mode: level, space, or distance (P001).
3. Set the response time to level changes (P003).
4. Select units of measurement: m, cm, mm, ft, or in. (P005).
5. Set process empty level (Empty: P006).
6. Set the range to be measured (Span: P007).
7. Set Auto False-Echo Suppression Distance (P838).
8. Enable Auto False-Echo Suppression (P837).
9. Return to RUN mode.
Note
• In PROGRAM mode, you can use the ARROW keys to scroll to a parameter number.
• The default parameter values are indicated by an asterisk (*) in the tables.
Using the handheld programmer, set each parameter value to suit your application.
34
then ENTER
, to Clear All and initiate reset. The LCD displays
to toggle between units and percentage.
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC