MOUNTING

06
Mounting

6.1 Requirements for Mounting

WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not mount the product in areas containing highly flammable materials or gases.
Do not mount the product in potentially explosive atmospheres.
Basic Requirements
SMILE-S6-HV-INV (OUTDOOR) and SMILE-BAT-8.2PH (OUTDOOR) are suitable for
indoor and outdoor use.
SMILE-S6-HV-INV (INDOOR) and SMILE-BAT-8.2PH (INDOOR) and
SMILE-BAT-5PH (INDOOR) are suitable for only indoor use.
Do not install the inverter in a place where a person can easily touch because its
housing and heatsink are hot during operation.
Do not mount the product in areas with flammable or explosive materials.
Do not mount the product at a place within children's reach.
Do not mount the product outdoors in salt areas because it will be corroded and may
cause fire. A salt area refers to the region within 500m from the coast or prone to sea
breeze. The regions prone to sea breeze vary depending on weather conditions (such
as typhoons and monsoons) or terrains (such as dams and hills).
Mounting Environment Requirements
The product must be mounted in a well-ventilated environment to ensure good heat
dissipation.
When mounted under direct sunlight, the power of the product may be derated due
to additional temperature rise.
Mount the product in a sheltered place or mount an awning over the product.
The optimal temperature range for the battery pack to operate is from15 to 30℃.
Do not expose or place near water sources like downspouts or sprinklers.
If the battery pack is mounted in the garage, then ensure that it is above the height of
the vehicle bumper and door.
Mounting Structure Requirements
The mounting structure where the product is mounted must be fireproof.
Do not mount the product on flammable building materials.
Ensure that the mounting surface is solid enough to bear the weight load.
In residential areas, do not mount the inverter on drywalls or walls made of similar
materials which have a weak sound insulation performance. Because the noise gener-
ated by the inverter is obvious.
20
21
Mounting Angle and Stack Requirement
SMILE-BAT-8.2PH should be floor-mounted.
SMILE-S6-HV-INV and SMILE-BAT-5PH should be wall-mounted.
The installation angle requirement is as follow:
• Do not mount the battery pack and inverter at forward tilted, back tilted, side tilted,
horizontal, or upside down positions.
Mounting Space Requirements
• Reserve enough space around the battery pack and inverter to ensure sufficient space
for installation, maintenance and heat dissipation.