SCREEN 66 (CFM Monitor
Option)
CFM LOW SETPOINT
1430
SCREEN 67 (Dewpoint Monitor
or Dewpoint Control)
DEWPOINT ALARM
ACT -20°F
180 SEC
SCREEN 68
DEWPOINT DEVIATION
SCREEN 71
HIGH
5°F
30 SEC
SCREEN 69
DEWPOINT DEVIATION
LOW 5°F
30 SEC
F u n c t i o n
This screen shows the low CFM setpoint.
The default is 1 CFM. The default can be
changed with the proper password (see
page 4-31, screen 85).
This screen shows the alarm setpoint for a
Dewpoint alarm. With the proper
password, it can be changed (see page
4-31, screen 85). The defaults are -3°F
{-5°C} for 180 seconds. If the control
senses -3°F {-5°C} or higher for 180
seconds, the dryer will alarm.
This is the dewpoint high deviation alarm
value. With the proper password, it can be
changed (see page 4-31, screen 85). When
in dewpoint control, if the actual dewpoint
goes above the setpoint in screen 67 for
the set amount of time, the dryer will
alarm "Dewpoint Deviation High".
This is the dewpoint low deviation alarm
value. With the proper password, it can be
changed (see page 4-31, screen 85). When
in dewpoint control, if the actual dewpoint
goes below the setpoint by this value for
this amount of time, the dryer will alarm
"Dewpoint Deviation Low".