6 Electrical Connection
6.10.1 Ethernet Communication
The WiNet-S communication for Ethernet cannot be used simultaneously with A1 and B1
terminals for RS485 daisy chain.
step 1 (Optional) Strip the insulation layer of the communication cable with an Ethernet wire strip-
per, and lead the corresponding signal cables out. Insert the stripped communication cable
into the RJ45 plug in the correct order, and crimp it with a crimper.
Skip this step if a standard network cable with RJ45 plug is prepared.
step 2 Unscrew the swivel nut from the communication module and take out the inner sealing ring.
step 3 Unscrew the housing from the communication module.
84
1: RJ45 plug
User Manual
2: Protective cap