Machine Protection

This section explains functions for protecting the machine.

Reducing Noise and Leakage Current

The switching frequency of the Inverter's output transistor can be changed to reduce carrier noise and leakage
current from the motor.
Related Constants
Name
Con-
stant
Display
Number
Carrier fre-
quency
Select carrier wave fixed pattern.
selection
C6-02
Select F to enable detailed settings using
constants C6-03 to C6-07.
Carrier
Freq Sel
Carrier
Set the carrier frequency upper limit and
frequency
lower limit in kHz units.
C6-03
upper limit
The carrier frequency gain is set as fol-
*3
lows:
Carrier
With the vector control method, the
Freq Max
upper limit of the carrier frequency is
fixed in C6-03.
Carrier
frequency
C6-04
lower limit
*3
Carrier
Freq Min
Carrier fre-
quency
propor-
K is a coefficient that depends on the
tional gain
C6-05
setting of C6-03.
*3
C6-03 ≥ 10.0 kHz: K = 3
Carrier
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
Freq Gain
5.0 kHz > C6-03: K = 1
Carrier fre-
quency
Select the carrier frequency when open-
selection
loop vector 2 control is used.
for open-
1: 2 kHz
C6-11
loop vector
2: 4 kHz
2 control
3: 6 kHz
4: 8 kHz
Carrier
Freq Sel
* 1. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 2. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. This constant can be monitored or set only when F is set for C6-02.
* 4. Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 5. The maximum output frequency depends on the setting for the carrier frequency (refer to page 6-44).
* 6. This setting is for software versions PRG 1040 and later. The factory setting with software versions PRG 1039 and earlier depends on the Inverter
capacity.
Description
Carrier frequency
Output frequency x (C6-05) x K
Output
frequency
(Max. output frequency)
Control Methods
Change
Setting
Factory
during
V/f
Range
Setting
Opera-
V/f
with
tion
PG
1 to F
6
No
Q
Q
*2
*1
2.0 to
15.0
No
A
A
15.0
kHz
*2 *5
*1
0.4 to
15.0
No
A
A
15.0
kHz
*2 *5
*1
00 to
00
No
A
A
99
1
No
No
1 to 4
No
*6
*4
*4

Machine Protection

MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vec-
Vector
ter
tor
tor
1
2
No
Q
Q
224H
*4
A
A
No
225H
No
No
No
226H
No
No
No
227H
No
No
Q
22DH
*4
*4
6-
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents