Torque Detection: L6
User constants for the torque detection function are shown in the following table.
Name
Con-
stant
Display
Number
Overtorque/
0: Overtorque/undertorque
Under-
detection disabled.
torque
1: Overtorque detection only
detection
with speed agreement;
selection 1
operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation
continues after overtorque
(warning).
3: Overtorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
L6-01
operation).
5: Undertorque detection only
Torq Det 1
with speed agreement;
Sel
operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation
continues after overtorque
(warning).
7: Undertorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
Overtorque/
Under-
Vector control: Motor rated
torque
torque is set as 100%.
detection
L6-02
V/f control: Inverter rated cur-
level 1
rent is set as 100%.
Torq Det 1
Lvl
Overtorque/
Under-
torque
Sets the overtorque/under-
detection
L6-03
torque detection time in 1-sec-
time 1
ond units.
Torq Det 1
Time
Setting
Factory
Description
Range
Setting
0 to 8
0 to
300
0.0 to
10.0
Control Methods
Change
Open
during
V/f
Loop
Opera-
V/f
with
Vec-
tion
PG
tor
1
0
No
A
A
A
150%
No
A
A
A
0.1 s
No
A
A
A
User Constant Tables
MEMO-
Open
BUS
Flux
Loop
Page
Regis-
Vec-
Vec-
ter
tor
tor
2
A
A
4A1H
6-54
A
A
4A2H
6-54
A
A
4A3H
6-55
5-
65