When E1-03 is set to F (User-defined V/f pattern), you can set constants E1-04 to E1-10. If E1-03 is set to
anything other than F, you can only refer to constants E1-04 to E1-10. If the V/f characteristics are linear, set
E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points.
When changing control method, constants E1-07 to E1-10 will change to the factory settings for that
control method.
Be sure to set the four frequencies as follows:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
-128
6
Output voltage (V)
E1-05
(VMAX)
E1-13
(V Base)
E1-08
(VC)
E1-10
(VMIN)
E1-09
(FMIN)
Fig 6.69 User-Set V/f Pattern
E1-07
E1-06
(FB)
(FA)
Frequency (Hz)
E1-04
(FMAX)