YASKAWA Varispeed G7 Series Instruction Manual page 356

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7 Series:
Table of Contents

Advertisement

Name
Con-
stant
Display
Number
Mid. output
frequency 2
E1-11
Mid
Frequency B
Mid. output
Set only to fine-adjust V/f for the
frequency
output range. Normally, this setting
voltage 2
E1-12
is not required.
Mid Voltage
B
Base voltage
E1-13
Base Voltage
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when A1-02 (Control Method) is changed. (The factory settings of the open-loop vector 1 control are given.)
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. When E1-13 (Base Voltage) is set to 0.0, control is performed with E1-13 equal to E1-05 (Max. Voltage).
E1-05 and E1-13 are automatically set to the same values when autotuning is performed.
* 5. The setting range for open-loop vector 2 control is 0 to 66.0 (0 to 132.0 for PRG 103).
For the 400 V Class, there are limitations on the maximum output frequency depending on the setting for the carrier frequency and capacity.
The maximum output frequency for 400 V, 90 to 110 kW is 250 Hz. The maximum output frequency for 400 V, 132 to 300 kW is 166 Hz.
Setting Inverter Input Voltage
Set the Inverter input voltage correctly in E1-01 to match the power supply voltage. This set value will be the
standard value for the protection function and similar functions.
The overvoltage detection level (OV) and the braking transistor operation level (BTR) vary depending on the
input voltage as shown in the following table.
Inverter Class
200 V Class
400 V Class
* These are values of operation levels for braking transistors built in Inverters of 0.4 to 15 kW. Refer to YASKAWA AC Drive Option Braking Unit, Braking
Resistor Unit Installation Manual (TOBPC72060000/TOBPC72060001) for operation levels for separately-installed type Braking Resistor Units.
If selecting a fixed V/f pattern (E1-03 = 0 to E) in V/f control the values of the max. voltage (E1-05), the mid.
Output frequency voltage (E1-08), and the min. output frequency voltage (E1-10) will change if the value for
the input voltage setting (E1-01) is changed.
Setting
Description
Range
0.0 to
400.0
*5
0.0 to
255.0
*1
0.0 to
255.0
*1
E1-01 Setting
All values
Approx. 410 V
400 V or more
Approx. 820 V
Less than 400 V
Approx. 720 V
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
0.0 Hz
No
A
A
*3
0.0 V
No
A
A
*3
0.0 V
No
A
A
*4
OV Detection Level
BTR Operation Level
Approx. 394 V
Approx. 788 V
Approx. 682 V
Individual Functions
MEMO
Open
BUS
Flux
Loop
Regis-
Vec-
Vector
ter
tor
1
2
A
A
A
30AH
A
A
A
30BH
Q
Q
Q
30CH
123
6-