YASKAWA Varispeed G7 Series Instruction Manual page 168

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7 Series:
Table of Contents

Advertisement

Con-
stant
Number
Motor leak
inductance
E2-06
Leak Induc-
tance
Motor iron
saturation
coefficient 1
E2-07
Saturation
Comp1
Motor iron
saturation
coefficient 2
E2-08
Saturation
Comp2
Motor
mechanical
loss
E2-09
Mechanical
Loss
Motor iron
loss for
torque com-
E2-10
pensation
Tcomp Iron
Loss
Motor rated
output
E2-11
Mtr Rated
Power
Motor iron
saturation
coefficient 3
E2-12
Saturation
Comp3
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
* 4. The same capacity as that of the Inverter will be set if the constants are initialized.
* 5. Torque compensation compensates the torque reference after the torque limit.
-36
5
Name
Description
Display
Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This constant is automatically
set during autotuning.
Sets the motor iron saturation
coefficient at 50% of mag-
netic flux.
This constant is automatically
set during autotuning.
Sets the motor iron saturation
coefficient at 75% of mag-
netic flux.
This constant is automatically
set during autotuning.
Sets motor mechanical loss as
a percentage of motor rated
output (W).
Usually setting is not neces-
sary.
Adjust in the following cir-
cumstances:
• When torque loss is large
due to motor bearing.
• When the torque loss in the
pump or fan is large.
The set mechanical loss will
compensate for torque.
Sets motor iron loss in W
units.
Set the rated output of the
motor in units of 0.01 kW.
This constant is automatically
set during autotuning.
Sets the motor iron saturation
coefficient at 130% of mag-
netic flux.
This constant is automatically
set during autotuning.
Change
Setting
Factory
during
Range
Setting
Opera-
tion
0.0 to
18.2%
No
40.0
*1
0.00 to
0.50
No
0.50
0.00 to
0.75
No
0.75
0.0 to
0.0
No
10.0
*5
0 to
14 W
No
65535
*1
0.00 to
0.40
No
650.00
*4
1.30 to
1.30
No
1.60
Control Methods
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
V/f
with
Vec-
Vec-
Vec-
PG
tor
tor
tor
1
2
No
No
A
A
A
313H
No
No
A
A
A
314H
No
No
A
A
A
315H
No
No
No
A
A
316H
A
A
A
No
No
No
317H
Q
Q
Q
Q
Q
318H
No
No
A
A
A
328H
Page
ter
6-119
6-119
6-119
6-120
6-117
6-120