Storing Inverter Set Values in the Digital Operator (READ)
To store Inverter set values in the Digital Operator, make the settings using the following method.
Set 03-02 (Read permitted selection) to 1 (read permitted).
Step
Digital Operator Display
No.
1
2
3
4
5
6
INV→OP READING
7
8
An error may occur while saving to memory. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display.
Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using the Digital Oper-
ator Copy Function.)
Error Display
READ IMPOSSIBLE
-154
6
Table 6.1 READ Function Procedure
-ADV-
** Main Menu **
Press the Menu Key, and select advanced programming mode.
Programming
-ADV-
Initialization
Press the DATA/ENTER Key, and select the constants monitor display.
A1
- 00=1
Select Language
-ADV-
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
COPY Function
Key.
o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Funtion Sel
Press the DATA/ENTER Key, and select the constants setting display.
o3-01=
0
*0*
COPY SELECT
-ADV-
Copy Funtion Sel
Change the set value to 1 using the Increment Key.
o3-01=
1
*0*
INV→OP READ
-ADV-
READ
Set the changed data using the DATA/ENTER Key. The READ function will start.
-ADV-
READ
If the READ function ends normally, End is displayed on the Digital Operator.
READ COMPLETE
-ADV-
Copy Funtion Sel
The display returns to o3-01.
o3 - 01=0
*0*
COPY SELECT
PRE
You are attempting to set o3-01 to 1 while o3-02 is set to 0.
Explanation
Meaning