Using Inverters for Elevating Machines
This section describes precautions to be observed when using the Varispeed G7 for elevating machines
such as elevators and cranes.
IMPORTANT
Brake ON/OFF Sequence
Brake ON/OFF Sequence
For the holding brake's ON/OFF sequence, use the following Inverter output signals according to the set con-
trol method.
Control Method
V/f with PG (A1-02 = 1)
Open-loop vector 1 (A1-02 = 2,
Flux vector (A1-02 = 3)
IMPORTANT
* 1. This example shows multi-function output terminals M1-M2 used for the holding brake ON/OFF signal.
Do not set H2-01 to 0 (During run).
* 2. This is the standard setting range for open-loop vector 1 control. For V/f control, set to approximately the motor rated slip frequency +0.5 Hz.
If the set value is too low, the motor torque is insufficient and the load may slip when the brake is applied. Be sure to set L4-01 to a value larger than that
of E1-09 (Min. output frequency) and larger than that of L4-02 shown in Figure 6.86. If the set value is too large, the motor may not run smoothly when
it starts running.
* 3. The hysteresis in frequency detection 2 can be adjusted (from 0.1 to 0.5 Hz) by L4-02 (speed agree detection width). Change the setting to approxi-
mately 0.1 Hz if there are drops while stopping.
* 4. Applicable for G7-Series Inverters with software versions PRG 1038 and later.
* 5. When using frequency detection 2, set L4-01 before H2-01. If H2-01 is set before L4-01, the holding brake will engage while stopping. For Inverters
with software versions PRG 1038 and later, use frequency detection 5 in which a holding brake signal is OFF when the Inverter is baseblocked.
Output frequency
Frequency detection 2
-172
6
When performing trial operation, enable Current alarm function (L8-41 =1), and be sure to make adjustments
to the braking sequence by using Peak hold functions (refer to Current Alarm Function and Peak Hold Cur-
rent Monitoring Function in Chapter 6 ) so that the startup current is less than 150% of the Inverter rated cur-
rent.
Signal Name
Frequency detec-
V/f (A1-02 = 0)
Frequency detec-
factory setting)
During run 2
Do not set Open-loop vector 2 for use in elevating machines.
L4-01
Brake ON/OFF Signal
*1
Constant
*5
H2-01 = 05
tion 2
*5
H2-01 = 36
*4
tion 5
H2-01 = 37
ON
Fig 6.86
Brake ON/OFF Level Adjustment
Signal Name
Constant
• L4-01 = 1.0 to
• Speed agree
detection level
3.0 Hz
• Speed agree
• L4-02 = 0.1 to
detection width
0.5 Hz
Zero-speed level
b2-01 = 0.1 to
(OFF timing only)
0.5 Hz
L4-02
Time
OFF
*2
*3